Post-occupancy evaluation for energy conservation, superior IEQ & increased occupant satisfaction

PARK, Ji Hyun, AZIZ, Azizan and LOFTNESS, Vivian (2013). Post-occupancy evaluation for energy conservation, superior IEQ & increased occupant satisfaction. Proceedings of IFMA's World Workplace 2013 Conference and Expo. [Article]

Documents
24087:526109
[thumbnail of No archiving policy]
PDF (No archiving policy)
J.Park_IFMA.pdf - Accepted Version
Restricted to Repository staff only
Available under License All rights reserved.

Download (953kB)
Abstract
This paper proposes a method comprising procedures to calibrate an EnergyPlus whole building energy model. An occupant behavior data mining procedure is developed and tested in an office building. Workday occupancy schedules are generated by mining the office appliance energy consumption data. Hourly and monthly power, energy, and temperature data are collected and used for lighting, equipment and HVAC systems energy performance calibration. The result shows a 1.27% mean bias error for the total annual energy use intensity. The proposed calibration method provides a scientific and systematic framework to conduct high accuracy EnergyPlus model calibration.